The monitoring of conductivity-controlled blowdown in open cooling circuits requires precise control of the automatic blowdown valve within the conductivity range specified by the customer. By connecting conductivity probes, e.g. the NeoTec Select, via 4-20 mA or Modbus, the NeoTecMaster® enables a reliable control concept and ensures proper desalination to guarantee the required cooling capacity and water quality. By means of bus connection, relay modules can be connected to the NeoTecMaster® for controlling the flush valve and other actuators.
This controller-based monitoring technology ensures data transfer via Ethernet interface to higher-level control stations. Visualization of the measured data can be implemented in the network directly at the site.
The modular NeoTecMaster® concept with its device periphery enables measurement of up to 8 parameters. In addition to conductivity determination, the Testomat® LAB TH can be integrated for water hardness measurement in make-up water and pH and redox measurement in cooling water, both on the basis of existing measurement technology and using innovative NeoTecMaster® Select probes.
Filter products
Testomat LAB Monochloramine – Analyzer for Monochloramine Continuous measurement of monochloramine using the DPD method The Testomat LAB Monochloramine NH2CL is an online analyzer designed for the continuous photometric determination of monochloramine in process and drinking water. The measuring range for monochloramine (NH2CL, calculated as Cl2) is 0 to 5 ppm (resolution 0.1). The analysis is performed by dosing two reagents. After a reaction time of approximately 60 seconds, the measurement result is available. The Testomat LAB NH2CL has been developed for use in multi-parameter systems and for connection to higher-level control systems. Key performance features of the Testomat LAB for monochloramine measurement Maintenance requirements are low thanks to minimal reagent consumption and optimized water detection. A multilingual menu structure as well as parameterization via SD card or the Servicemonitor software make installation and adaptation to individual measurement tasks particularly user-friendly. In addition to the 4–20 mA output for transmitting measurement values, this series is equipped with an RS232 interface for transmitting measurement data as well as error and status messages. All data are continuously recorded on the integrated SD card or an optional SDHC card (2 GB) in CSV format and are available at any time for detailed evaluation. Technical highlights and performance profile of the Testomat LAB for monochloramine monitoring Technical features include peristaltic pumps, a space-saving design, automatic venting of the indicator line, an integrated self-test, and firmware update capability via SD card. The Monochloramine NH2CL and NH2CL-R stand out with the following functionalities: RS232 interface for transmission of measurement values and error messages Parameterization via SD card or the “Servicemonitor” software (Mini-USB device side to USB 2.0, e.g. PC or notebook) Multilingual menu navigation (German, English, French, Dutch) Firmware update via SD card Compact design Optimized water detection based on an optical measurement principle Integrated self-test with continuous monitoring Optimized reagent set with reduction from three to two reagents Proven performance profile Highly accurate peristaltic pumps Reliable, low-maintenance operation Minimal reagent and water consumption 4–20 mA analog output for transmission of measurement values RS232 interface for transmission of measurement values and fault messages Common alarm output Optimized reagents: only two reagents required for monochloramine determination Optimized reagent containers with matched fill volumes so that both containers are depleted at the same time Additional functions of the NH2CL-R version Parameterization and reading of device parameters via the RS232 interface. Analysis triggering: Automatic interval operation (interval pause adjustable from 10 to 60 minutes) Measurement phase mode (start signal triggers a sequence of analyses for 10 minutes up to 12 hours) External analysis input (start/stop) Manual start Optional accessories OLED display Protective cover to increase the IP protection class Where can the Testomat be used? Monitoring water quality in water treatment and drinking water systems Process monitoring Monitoring monochloramine concentration in cooling tower processes Connection to higher-level control systems
The Testomat® LAB Monochloramine (NH2CL) is an online analyser that photometrically measures the content of monochloramine in process water and is used for continuous monitoring of process quality, for example in cooling circuits. Another area of application is the use in the environment of water treatment and drinking water plants, for process monitoring, as well as monitoring the decay behaviour in cooling towers after shock chlorination. The measuring range for monochloramine (NH2CL, calculated as Cl2) is 0 to 5 ppm (resolution 0.1). The instrument works according to the DPD method based on EN ISO 7393-2 and the analysis is carried out by adding two reagents. After a reaction time of approx. 60 seconds (dosing and measuring time without rinsing time) the measuring result is available. For the transmission of the measured values, in addition to the 4-20mA signal output, an RS232 interface is available for the transmission of the measured values as well as error & status messages. Furthermore, all data are continuously recorded on the integrated SD card or optionally available SDHC card (2Gbyte) as a file in CSV format and can be used for detailed observations at any time. In view of the fact that the Testomat® LAB Monochloramine was developed for use in multi-parameter systems or for connection to a higher-level control system, we hereby offer you the Testomat® LAB Monochloramine in conjunction with the NeoTecMaster® Multicontroller, which was specially developed by our company, as a package solution at a preferential price. The 4-channel NeoTecMaster® Multicontroller included in this package enables the processing of up to four measurement signals in this version. One signal input on the NeoTecMaster®, in this case the RS232 interface, is used by Testomat® LAB Monochloramine to display the measured value, the trend and the status messages on the 5 inch screen. In addition to the RS232 interface, the NeoTecMaster® also has a Modbus RTU input, which you can use freely after brief technical consultation with us. (Pre-check whether your existing measurement technology to be integrated requires adjustments). The NeoTecMaster® can be systematically supplemented with further optional NeoTec modules (function / signal converter modules) as required. This allows the future realisation of further control concepts in a flexible way. Two modules which fundamentally extend the range of functions and are already included in the scope of delivery are our NeoTec slave relay module and the 4x 4-20mA output module. This allows you to add potential-free relay contacts to the overall system and to realise linear or inverted dosing processes via the 4x 4-20mA output module. You can freely assign the relay contacts to the incoming measurement signals and thus, for example, also implement simple limit value-related control concepts, as well as output measurement value-related messages. Via the 4-20mA output module, you can also forward the measured values to a higher-level controller as desired. Further advantages of the NeoTecMaster: Simple operation Integration of the Testomat® world of instruments, here in connection with the Testomat® LAB Monochloramine Integration into the existing control cabinet, alternatively we offer you our NeoTecMaster® housing Modular range of functions can be extended by NeoTec slave and signal converter modules (measurement, control, regulation) Available as built-in or surface-mounted variant Structured continuous data recording on the integrated SD card or optionally available SDHC card (2Gbyte) as a file in CSV format In addition, there are proven Testomat® LAB functionalities: Optimised water detection based on an optical measuring method RS232 interface for transmission of measured values and error messages Import and export of settings (basic programming) Logging of measurement data and messages/alarms via integrated SD card or optionally usable SDHC card (2GByte) Firmware update via SD card Integrated self-test with continuous monitoring Automatic venting of the indicator line Performance profil Testomat® LAB Monochloramine: High-precision peristaltic pumps Reliable and low-maintenance operation Minimal reagent and water consumption Analog output 4 - 20 mA for transmission of measured values RS232 interface for transmission of measured values & fault messages Execution of parameterisation by means of SD card or "Service Monitor" software via mini-USB (on the unit side) to USB 2.0 (e.g. PC/notebook) Multilingual software menu in German, English, French, Dutch Compact design Common alarm output Optimised reagents: Only 2 reagents for the determination of monochloramine (NH2CL) Optimised reagent set: filling quantities are coordinated so that the reagent set is used up almost evenly Analysis triggering: Automatic interval operation (interval pause adjustable from 10-60 minutes) Measuring phase mode (start impulse triggers a sequence of analyses for a period of 10 minutes to 12 hours) External analysis input (start/stop) Hand start Optional accessories available: OLED display for Testomat® LAB Protective cover to increase the IP protection class of the Testomat® LAB NeoTecMaster instrument cover
The Testomat LAB TH and the Testomat LAB TH-R (Remote) are fully automatic online analyzers for the precise determination of residual total hardness in water using automated titration. The device provides continuous, reliable measurement results in the range of 0.05–25 °dH. The instruments were developed for use in multiparameter systems and for connection to higher-level control systems. Fully automatic residual hardness measurement for laboratory and process water using Testomat LAB High-precision titrimetric hardness determination with data logging The Testomat LAB TH combines high measurement accuracy with easy integration into existing measurement and automation concepts. Automatic titration using a piston dosing pump enables continuous, low-maintenance acquisition of water hardness values. All measurement data are logged in a structured format on an integrated SD card or optionally on an SDHC card. The standard interfaces 4–20 mA and RS232 allow direct data transfer to higher-level control and process control systems. Application areas of the Testomat LAB TH and LAB TH-R (Remote) Flexible use in laboratory, process, and drinking water monitoring Water treatment plants Drinking water systems Industrial boilers Process water monitoring Technical highlights and performance features of the Testomat LAB TH The Testomat LAB TH features optical water detection during filling of the measuring chamber, automatic venting of the indicator line, and an integrated self-test for continuous system monitoring. Benefits of hardness measurement within the LAB multiparameter system Thanks to the integration capabilities of the Testomat LAB in a manufacturer-independent multiparameter system, precise and continuous online monitoring of water hardness is possible within a central measurement platform. Automatic titrimetric measurement delivers reliable and reproducible results and can be easily integrated into existing process and control systems via standardized interfaces. This increases process reliability and reduces maintenance and personnel costs.
The Testomat® LAB TH determines the water hardness (residual total hardness) fully automatically by use of titration and has been developed for monitoring the water quality of water treatment plants, drinking water plants, industrial boilers and for monitoring process water and the Testomat® LAB CL is a robust, wet chemical online measuring converter to measure the concentration of total chlorine or free chlorine in the measuring range 0 - 5 mg/l. The instrument is suitable for controlling the water quality of water treatment plants, drinking water plants, process water monitoring and for monitoring the chlorine concentration in the cooling tower process. Instrument operation is based on the DPD method according to EN ISO 7393-2. The analysis is carried out through the addition of two reagents and the measurement result is obtained after a reaction time of approx. 60 seconds (pure measurement time without flush time). In view of the fact that the Testomat® LAB TH and Testomat® LAB CL was developed for use in multi-parameter systems or for connection to a higher-level control system, we hereby offer you both Testomat® LAB analysis devices in combination with the NeoTecMaster®, which was specially developed by our company, as a package solution at a preferential price. The 4-channel NeoTecMaster® multi-parameter controller included in this package enables the processing of up to four measurement signals in this version. A signal input on the NeoTecMaster® , in this case the RS232 interface and one additional RS232 interface on the included NeoTec Slave module , are used by Testomat® LAB TH and Testomat® LAB CL to display the measured value, the trend and the status messages on the 5 inch screen. In addition to the on board RS232 interface, the NeoTecMaster® also has a Modbus RTU input, which you can use freely after brief technical consultation with us. (Pre-check whether your existing measurement technology to be integrated requires adjustments). The NeoTecMaster® can be systematically supplemented with further optional NeoTec modules (function / signal converter modules) as required, thus enabling the future realisation of further control concepts in a flexible manner. A module that fundamentally expands the range of functions and is already included in the scope of delivery is our NeoTec slave relay module with which you can add potential-free relay contacts to the overall system. You can freely assign these to the incoming measurement signals and thus, for example, implement limit value-related control concepts, as well as output measurement-related messages. Further advantages of the NeoTecMaster: Simple operation Integration of the Testomat® world of instruments, here in conjunction with the Testomat® LAB TH and Testomat® LAB CL Integration into the existing control cabinet, alternatively we offer our NeoTecMaster® housing Modular range of functions can be extended by NeoTec slave and signal converter modules (measurement, control, regulation) Available as built-in or surface-mounted variant Structured continuous data recording on the integrated SD card or optionally available SDHC card (2Gbyte) as a file in CSV format In addition, there are proven Testomat® LAB functionalities: Optimised water detection based on an optical measuring method RS232 interface for transmission of measured values and error messages Import and export of settings (basic programming) Logging of measurement data and messages/alarms via integrated SD card or optionally usable SDHC card (2GByte) Firmware update via SD card Execution of parameterisation by means of SD card or "Service Monitor" software via mini-USB (on the unit side) to USB 2.0 (e.g. PC/notebook) Multilingual software menu in German, English, French, Dutch; Portuguese Integrated self-test with continuous monitoring Automatic venting of the indicator line Compact design Performance profil Testomat® LAB TH: High-precision titration by means of piston metering pump Reliable and low-maintenance operation Minimal indicator and water consumption Analogue output 4 - 20 mA for transmission of measured values Programmable hardness unit in °dH, °f, ppm CaCO3, mmol/l Collective alarm output Indicator quantities: 500 ml bottles Analysis trigger: - Automatic interval operation (interval pause adjustable from 0-255 minutes) - External analysis input (start/stop) - Manual start Performance profil Testomat® LAB CL: High-precision peristaltic pumps Reliable and low-maintenance operation Minimal reagent and water consumption Analog output 4 - 20 mA for transmission of measured values RS232 interface for transmission of measured values & fault messages Common alarm output Optimised reagents: Only 2 reagents for the determination of total chlorine Optimised reagent set: filling quantities are coordinated so that the reagent set is used up almost evenly. Analysis trigger: Automatic interval operation (interval pause adjustable from 0-255 minutes) External analysis input (start/stop) Manual start Optional accessories available: OLED display Protective cover to increase the IP protection class of the Testomat® LAB devices NeoTecMaster instrument cover
The Testomat® LAB TH determines the water hardness (residual total hardness) fully automatically by use of titration and has been developed for monitoring the water quality of water treatment plants, drinking water plants, industrial boilers and for monitoring process water. In view of the fact that the Testomat® LAB TH was developed for use in multi-parameter systems or for connection to a higher-level control system, we hereby offer you the Testomat® LAB TH in combination with the NeoTecMaster®, which was specially developed by our company, as a package solution at a preferential price. The 4-channel NeoTecMaster® multi-parameter controller included in this package enables the processing of up to four measurement signals in this version. A signal input on the NeoTecMaster®, in this case the RS232 interface, is used by Testomat® LAB TH to display the measured value, the trend and the status messages on the 5 inch screen. In addition to the RS232 interface, the NeoTecMaster® also has a Modbus RTU input, which you can use freely after brief technical consultation with us. (Pre-check whether your existing measurement technology to be integrated requires adjustments). The NeoTecMaster® can be systematically supplemented with further optional NeoTec modules (function / signal converter modules) as required, thus enabling the future realisation of further control concepts in a flexible manner. A module that fundamentally expands the range of functions and is already included in the scope of delivery is our NeoTec slave relay module with which you can add potential-free relay contacts to the overall system. You can freely assign these to the incoming measurement signals and thus, for example, implement limit value-related control concepts, as well as output measurement-related messages. Further advantages of the NeoTecMaster: Simple operation Integration of the Testomat® world of instruments, here in conjunction with the Testomat® LAB TH Integration into the existing control cabinet, alternatively we offer our NeoTecMaster® housing Modular range of functions can be extended by NeoTec slave and signal converter modules (measurement, control, regulation) Available as built-in or surface-mounted variant Structured continuous data recording on the integrated SD card or optionally available SDHC card (2Gbyte) as a file in CSV format In addition, there are proven Testomat® LAB TH functionalities: Optimised water detection based on an optical measuring method RS232 interface for transmission of measured values and error messages Import and export of settings (basic programming) Logging of measurement data and messages/alarms via integrated SD card or optionally usable SDHC card (2GByte) Firmware update via SD card Execution of parameterisation by means of SD card or "Service Monitor" software via mini-USB (on the unit side) to USB 2.0 (e.g. PC/notebook) Multilingual software menu in German, English, French, Dutch, Portoguese Integrated self-test with continuous monitoring Automatic venting of the indicator line Compact design Proven performance profil: High-precision titration by means of piston metering pump Reliable and low-maintenance operation Minimal indicator and water consumption Analogue output 4 - 20 mA for transmission of measured values Programmable hardness unit in °dH, °f, ppm CaCO3, mmol/l Collective alarm output Indicator quantities: 500 ml bottles Analysis trigger: - Automatic interval operation (interval pause adjustable from 0-255 minutes) - External analysis input (start/stop) - Manual start Optional accessories available: OLED display Protective cover to increase the IP protection class of the Testomat® LAB TH NeoTecMaster instrument cover
The Testomat LAB TH and the Testomat LAB TH-R (Remote) are fully automatic online analyzers for the precise determination of residual total hardness in water using automated titration. The device provides continuous, reliable measurement results in the range of 0.05–25 °dH. The instruments were developed for use in multiparameter systems and for connection to higher-level control systems. Fully automatic residual hardness measurement for laboratory and process water using Testomat LAB High-precision titrimetric hardness determination with data logging The Testomat LAB TH combines high measurement accuracy with easy integration into existing measurement and automation concepts. Automatic titration using a piston dosing pump enables continuous, low-maintenance acquisition of water hardness values. All measurement data are logged in a structured format on an integrated SD card or optionally on an SDHC card. The standard interfaces 4–20 mA and RS232 allow direct data transfer to higher-level control and process control systems. Application areas of the Testomat LAB TH and LAB TH-R (Remote) Flexible use in laboratory, process, and drinking water monitoring Water treatment plants Drinking water systems Industrial boilers Process water monitoring Technical highlights and performance features of the Testomat LAB TH The Testomat LAB TH features optical water detection during filling of the measuring chamber, automatic venting of the indicator line, and an integrated self-test for continuous system monitoring. Benefits of hardness measurement within the LAB multiparameter system Thanks to the integration capabilities of the Testomat LAB in a manufacturer-independent multiparameter system, precise and continuous online monitoring of water hardness is possible within a central measurement platform. Automatic titrimetric measurement delivers reliable and reproducible results and can be easily integrated into existing process and control systems via standardized interfaces. This increases process reliability and reduces maintenance and personnel costs.