Features and Equipment

Optical water detection when filling the measuring chamber ensures precise dosing. Additionally, the device features automatic venting of the indicator line, an integrated self-test, and a multilingual menu. Measurement data and messages/alarms are logged via an integrated SD card or optional SDHC card. Recorded values and alarms can be transmitted for external processing via an analog 0/4–20 mA output or the RS232 interface.

Applications of the Testomat EVO TH CAL

  • Monitoring hardness in water treatment systems
  • Water hardness measurement in drinking water systems
  • Fully automatic hardness measurement in industrial boilers
  • Process water monitoring

Continuous monitoring of water hardness enables reliable process control in water treatment, drinking water, and industrial systems. Scale deposits, corrosion, and energy losses are reduced, legal limits are safely maintained, and equipment lifespan is extended. Deviations in water hardness are detected early, improving operational safety, product quality, and efficiency.

Benefits of the Testomat EVO TH CAL in Daily Operation

The Testomat EVO TH CAL features minimal water and indicator consumption as well as simple data management. With a freely programmable password, external reset and acknowledgment inputs, and the ability to adapt to temporarily low water pressure, the device is suitable for demanding environments.

Dimensions

Height 48 cm
Length 28 cm
Width 38 cm

Weight

Weight 9,12 kg

Other attributes

Country of origin EU
Customs tariff number 90278990
Technical specifications
Supply voltage: switching power supply 100-240 VAC, 100-353 VDC
Power consumption: max. 30 VA
Protection class: I
Protection: IP 44
Ambient temperature: 10–40 °C
Water temperature: 10–40 °C
Dimensions (W x H x D):     380 x 480 x 280 mm
Operating pressure: 1 bis 8 bar / 1x105 bis 8x105 Pa Oder 0,3* bis 1 bar / 0,3x105 bis 1x105 Pa (after removal of the valve body)
Weight: approx. 9,0 kg
Menu Language: German, English, French, Dutch, Spanish, Turkish, Chinese, Czech, Russian (others on request)
Measuring range: Water hardness: 0.89 - 448 ppm